Description
Accurately assess lead-acid battery deterioration using proprietary technology
The new Battery Tester BT3554-50 sets a new standard for UPS and lead-acid battery diagnostics. Since the battery’s internal resistance and voltage are measured using the impedance method, diagnostics can be performed while the battery is connected to its host device, without taking it offline. Proprietary noise reduction technology allows more accurate measurement, even in noisy environments.
Enjoy measurement guidance and easy data management functionality with the latest software
When the BT3554-50 is paired with a dedicated mobile app (GENNECT Cross), the mobile device will provide audio guidance announcing the next battery number to be measured. This feature helps prevent erroneous measurements. You can also set up measurement locations information’s and battery numbers in advance to create profiles to which measurement data and diagnostic results will be linked. This capability simplifies data management, even when performing diagnostic work on large numbers of batteries.
How to use Battery Testers: Observing Measurement Results Captured Wirelessly on a Mobile Device
Measured values captured by the Hioki BT3554-50 Battery Tester with Bluetooth wireless technology can be displayed and saved onto a mobile device wirelessly. (When using the Wireless Adapter Z3210)
The results can also be used to create automatic reports. Simply install the free GENNECT Cross app onto your mobile device and connect to the Hioki BT3554-50. Reports created on your mobile device can even be e-mailed to the office to further increase work efficiency. Data uploaded by the Gennect Cross app can also be loaded into a PC to view the historical state of the specified battery as a graph.
Generating comparative judgments based on a lead-acid battery’s internal resistance and voltage
By using its comparator function to simultaneously measure the internal resistance and voltage of a lead-acid, nickel-cadmium, or nickel-hydride battery, the BT3554-50 can generate comparative judgments quantifying degradation of the cell based on user-specified threshold values.
Furthermore, voltage sign detection facilitates instantaneous determination of whether batteries have been connected properly in newly installed UPS systems.
Saving data easily just by placing the leads in contact with a battery’s terminals
The BT3554-50 auto-hold function automatically holds measured values once they stabilize. The instrument’s auto-memory function, which automatically stores measured values resulting from the auto-hold function in its internal memory, further streamlines work tasks.
Basic Specifications
BT3554-50 | BT3554-51 | BT3554-52 | ||||
Resistance measurement range | 3 mΩ (max. display 3.100 mΩ, resolution 1 μΩ) to 3 Ω (max. display 3.100 Ω, resolution 1 mΩ), 4 ranges Accuracy: ±0.8 % rdg ±6 dgt (3 mΩ range: ±1.0 % rdg ±8 dgt) Testing source frequency: 1 kHz ±30 Hz With function for avoiding noise frequency enabled: 1 kHz ±80 Hz Testing current: 160 mA (3m/30 mΩ range), 16 mA (300 mΩ range), 1.6 mA (3 Ω range) Open terminal Voltage: 5 V peak |
|||||
Voltage measurement range | ± 6 V (max. display ±6.000 V, resolution: 1 mV) to ± 60 V (max. display ±60.00 V, resolution: 10 mV), 2 ranges, Accuracy: ±0.08 % rdg ±6 dgt | |||||
Temperature measurement accuracy | Measurement range: -10°C to 60°C (14°F to 140°F), Maximum display: 60.0°C (140.0°F), Resolution 0.1°C (0.1°F), Measurement accuracy*: ±1.0°C (±1.8°F) * When using the Clip Type Lead with Temperature Sensor 9460. * When using the Temperature Probe 9451, add ±0.5°C (±0.9°F) (cable length: 1.5 m [59.1″]). * When using the Temperature Probe 9451S, add ±0.5°C (±0.9°F) (cable length: 0.1 m [3.94″]). BT3554-50 standalone accuracy with simulated input: ±0.5°C (±0.9°F) |
|||||
Absolute max. input voltage | 60 V DC max. (No AC input) | |||||
Measurement time | 100 ms | |||||
Response time | Approx. 1.6 sec. | |||||
Comparator | Compares measured values with set threshold values to make judgments and reports them to the user. Judgment notification method: Results are displayed as shown below (segment) and beeping tones sound When the Voltage value (high): Resistance value (low)= PASS, Resistance value (medium)= WARNING, Resistance value (high)= FAIL When the Voltage value (low): Resistance value (low)= WARNING, Resistance value (medium)= WARNING, Resistance value (high)= FAIL If the judgment result is WARNING or FAIL, the audio tone is accompanied by a red backlight. User-selectable voltage judgment method: ABS (absolute value judgment), POL (polarity judgment ) Savable settings: 200 tables |
|||||
Memory functionality | Operation: Save, load, and delete measurement data, Save and delete profile information, Number of data sets: 6000, Memory architecture: 500 data sets per unit (12 units) Saved data: Saved measurement data is linked to profile information.1. Measurement data: Data can be saved, loaded, and deleted by operating the instrument. -1. Date and time -2. Resistance value, voltage value, and temperature -3. Comparator threshold value and judgment result2. Profile information: Profile information can be saved, loaded, and deleted using a supported application (GENNECT Cross or GENNECT One). -1. Profile numbers: 1 to 100 (Data (2), (3), and (4) below are saved for each profile number) -2. Location: User-defined comment such as location of UPS -3. Device information: User-defined comment such as UPS management number -4. Battery number: 1 to 500 (start number, end number) |
|||||
Measurement Navigator | Operation: Announces the next battery number to be measured via a screen display and audio guidance. Audio output is generated by a connected mobile device when using the Z3210 and a supported application (GENNECT Cross). Preparations: Profile information that’s been registered with a supported application (GENNECT Cross or GENNECT One) must be transferred to the instrument. |
|||||
Communication interface | USB Bluetooth® wireless communications (when Z3210 installed) |
|||||
Other functions | Temperature measurement (-10.0 to 60.0 °C), Zero-adjustment, Hold, Auto-hold, Auto-memory, Auto-power-save, Clock | |||||
Power supply | LR6 (AA) Alkaline dry battery ×8 Continuous operating time: About 8.3 hr. (without Z3210 installed), About 8.2 hr. (with Z3210 installed and wireless communications active) |
|||||
Dimensions and mass | 199 mm (7.83 in)W × 132 mm (5.20 in)H × 60.6 mm (2.39 in)D (with protector), 960 g (33.9 oz) (including batteries and protector) | |||||
Accessories | Carrying Case C1014 ×1, Protector Z5041 ×1, Fuse Set Z5050 ×1, 0 Adj Board ×1, Neck strap ×1, USB cable ×1, Application software CD (GENNECT One) ×1, AA alkaline battery (LR6) ×8, User Manual ×1 | |||||
Instrument only | With Pin Type Lead 9465-10 | With Pin Type Lead L2020 |